Electrician — Technical Calculators

Cable cross-sections, breakers, load budgets, backup generators, three-phase balancing, lighting, and earthing.

13 tools·4 every day·No account required·Unicode PDF export
All trades portal

Electrician · 13 calculators

Every day · Calculation · 6 inputs

Which cable size?

What cable cross-section prevents overheating and keeps voltage drop within limits over 60 m?

Inputs, outputs & calculation rule▾
Inputs
  • Known electrical value
  • Active power
  • Load current (I)
  • System / Voltage
  • One-way cable run length
  • Conductor & circuit type
Results
  • Recommended cable cross-section
  • Operating current (I)
  • Voltage drop (%)
  • Voltage drop (V)
  • Indicative ampacity (Iz, method B1 PVC)
  • Rejected size just below (6 mm²)
Calculation ruleΔU = 2 × ρ × L × I ÷ S (1-ph/DC) · ΔU = √3 × ρ × L × I ÷ S (3-ph) · Selected size = smallest standard cross-section meeting both max ΔU% and Iz ≥ I.
#tool
Every day · Calculation · 5 inputs

Which circuit breaker for this load?

Connecting an AC, water heater, or pump: what circuit breaker and cable size?

Inputs, outputs & calculation rule▾
Inputs
  • Appliance / circuit type
  • Appliance power
  • Power supply
  • Distance from distribution board
  • Socket / Wet room / Domestic circuit (30 mA)
Results
  • Recommended circuit breaker
  • Copper cable cross-section
  • Design current (Ib)
  • 30 mA protection
  • Tripping curve
  • Cable ampacity (Iz)
Calculation ruleIb = P ÷ (U × cos φ) · Standard breaker In ≥ Ib and ≤ cable ampacity Iz · 30 mA RCD required for sockets, wet areas, and domestic circuits.
#tool
Every day · Calculation · 6 inputs

Watts, amps and kVA

How many amps is a 5 kVA generator? What about a 2,000 W AC?

Inputs, outputs & calculation rule▾
Inputs
  • Known quantity
  • Apparent power
  • Active power
  • Electric current
  • Supply voltage
  • Power factor (cos φ)
Results
  • Calculated current
  • Current (A)
  • Active power (W)
  • Active power (kW)
  • Apparent power (kVA)
Calculation rule1-ph: P = U × I × cos φ · S = U × I · 3-ph: P = √3 × U × I × cos φ · S = √3 × U × I · kVA = kW ÷ cos φ.
#tool
Every day · Calculation · 6 inputs

Verify an existing cable

Is this existing 4 mm² cable over 45 m safe for this load?

Inputs, outputs & calculation rule▾
Inputs
  • Installed cable cross-section
  • Cable length
  • Conductor & circuit usage
  • Load input mode
  • Connected load power
  • Supply voltage
Results
  • Measured voltage drop
  • Current drawn (I)
  • Voltage drop (V)
  • Allowed limit
  • Indicative max current (Iz)
Calculation ruleΔU = 2 × ρ × L × I ÷ S (1-ph) · √3 × ρ × L × I ÷ S (3-ph) · Checks both voltage drop (3% lighting / 5% other) and permissible ampacity Iz.
#tool
Every week · Calculation · 3 inputs

Electrical load schedule

What main breaker rating is needed for this house or shop?

Inputs, outputs & calculation rule▾
Inputs
  • Installed loads
  • Supply system
  • Site type (diversity)
Results
  • Recommended main breaker
  • Total installed power
  • Simultaneous demand power
  • Calculated current
  • Apparent power (kVA)
  • Subscription rating (at breaker)
Calculation ruleDemand P = Σ(P × qty × use factor) × diversity factor · I = P ÷ (U × cos φ) or ÷ (√3 × 400 × cos φ).
#tool
Every week · Estimate · 5 inputs

Generator & backup sizing

What generator kVA or inverter/battery backup runs AC, fridge and pump during outages?

Inputs, outputs & calculation rule▾
Inputs
  • Continuous load to back up
  • Includes motors, pump or AC
  • Largest motor / AC unit power
  • Target outage duration (hours)
  • Inverter option: battery voltage
Results
  • Recommended generator size
  • Base generator kVA (×1.25)
  • Starting surge kVA
  • Fuel rate (diesel est.)
  • Fuel for 4 h
  • Equivalent inverter
Calculation rulekVA = W ÷ 0.8 × 1.25 · motor/AC startup × 3 to × 6 · diesel ≈ 0.3 L/kWh · battery Ah = (W × h) ÷ (V × 0.8 × 0.85).
#tool
Every week · Estimate · 5 inputs

Building circuits & cable estimator

5-room house: how many circuits, cable lengths, outlets, switches and breakers?

Inputs, outputs & calculation rule▾
Inputs
  • Number of rooms
  • Total socket outlets
  • Lighting points
  • AC units (dedicated circuits)
  • Water heaters / heavy appliances
Results
  • Total circuits to wire
  • Lighting circuits (1.5 mm² · 10/16 A)
  • Socket circuits (2.5 mm² · 20 A)
  • Dedicated circuits (2.5/4 mm² · 20–32 A)
  • 30 mA RCDs (differential)
  • 1.5 mm² cable (3G1.5 or 3×1.5)
Calculation ruleLighting 1.5 mm² (10/16 A, ≤ 8 pts) · sockets 2.5 mm² (20 A, ≤ 8 sockets) · dedicated circuit for each AC unit and water heater.
#tool
Every week · Calculation · 5 inputs

3-phase load balancing

How to distribute single-phase loads across L1, L2 and L3 and check imbalance?

Inputs, outputs & calculation rule▾
Inputs
  • Analysis mode
  • Phase L1 current (A)
  • Phase L2 current (A)
  • Phase L3 current (A)
  • Loads to balance
Results
  • Phase imbalance
  • Average phase current
  • Phase L1
  • Phase L2
  • Phase L3
  • Max − Min spread
Calculation ruleImbalance = (I max − I avg) ÷ I avg × 100 · target less than 10%.
#tool
Every week · Calculation · 3 inputs

Conduit & trunking fill size

How many wires fit in a 25 mm conduit, or what conduit/trunking size is needed?

Inputs, outputs & calculation rule▾
Inputs
  • Number of wires / cables
  • Conductor cross-section
  • Conduit size to check
Results
  • Recommended ICTA conduit
  • Insulated wire area (all)
  • Check in Ø 25 mm conduit
  • Max wires in Ø 25 mm (1/3 rule)
  • Recommended trunking
Calculation rule1/3 fill rule: total insulated conductor area (π × d² ÷ 4) ≤ ⅓ of internal conduit area.
#tool
Every week · Calculation · 5 inputs

Room LED lamp calculator

How many LED lamps are needed for this living room, office or shop?

Inputs, outputs & calculation rule▾
Inputs
  • Room floor area
  • Room type (target lux)
  • Target illuminance (lux)
  • Luminous flux per lamp (lm)
  • Power per lamp (W)
Results
  • Number of lamps needed
  • Exact theoretical count
  • Target illuminance
  • Achieved illuminance
  • Total lighting power
Calculation ruleN = (target lux × m²) ÷ (lamp lumens × utilization factor 0.5) · living room 150–200 lux, office/kitchen 300–500 lux.
#tool
Now and then · Calculation · 4 inputs

Appliance energy consumption (kWh)

How many kWh per day and per month does this appliance consume?

Inputs, outputs & calculation rule▾
Inputs
  • Electrical power draw
  • Hours of use per day
  • Days per month
  • Effective duty cycle (%)
Results
  • Monthly energy consumption
  • Daily consumption
  • Estimated annual consumption
  • Effective average power
Calculation rulekWh = W × hours ÷ 1,000 · Adjusted by duty cycle factor if intermittent.
#tool
Now and then · Calculation · 4 inputs

Power factor correction (kVAr)

What capacitor bank size (kVAr) to raise power factor from 0.70 to 0.95?

Inputs, outputs & calculation rule▾
Inputs
  • Active load power
  • Current cos φ
  • Target cos φ
  • 3-phase line voltage (V)
Results
  • Capacitor bank power
  • tan φ before → after
  • Apparent power before / after
  • Line current at 400 V
Calculation ruleQc = P × (tan φ1 − tan φ2) · Reduces apparent power (kVA) and line current.
#tool
Now and then · Estimate · 4 inputs

Earthing rods & resistance estimator

How many ground rods are needed to reach the target earth resistance?

Inputs, outputs & calculation rule▾
Inputs
  • Soil type (resistivity ρ)
  • Ground rod length
  • Number of rods installed
  • Target max resistance (Ω)
Results
  • Estimated earth resistance
  • Single rod estimate (ρ ÷ L)
  • Rods needed to reach ≤ 15 Ω
  • Min spacing between rods (2 × L)
  • Soil resistivity assumed (ρ)
Calculation ruleSingle rod: R ≈ ρ ÷ L · n rods spaced ≥ 2 × L apart: R ÷ n · verify with earth tester
#tool

Explore related trade calculators

Keep your pinned tools inside CTL-DOC

Your pinned calculators stay ready on mobile and offline PC, organized by job site alongside your full CTL-DOC workspace.